Liyv Tinned Copper Conductor to IEC 60228 Class 5 Fine Wire Stranded Control and Instrumentation Cable Single Core Non-Sheathed Electric Wire
CABLE CONSTRUCTION
Conductor Tinned copper-conductor, to DIN VDE 0295 cl.5, fine-wire, BS 6360 cl.5, IEC 60228 cl.5
Insulation Core insulation of PVC compound type YI3 to DIN VDE 0812
TECHNICAL DATA
PVC single cores adapted to DIN VDE 0812
| Temperature range | flexing – 5℃ to +70℃, fixed installation - 30℃ to 80℃ |
| Operating peak voltage | 0,14 mm² = 500 V, 0,25 – 1,5 mm² = 900 V |
| Test voltage | 0,14 mm² = 1200 V, 0,25 – 1,5 mm² = 2500 V |
| Insulation resistance | min . 10 MΩ x km |
| Minimum bending radius | fixed installation 4x core Ø |
PVC self -extinguishing and flame retardant acc. to DIN VDE 0482 – 332 – 1 – 2, DIN EN 60332 – 1 – 2, IEC 60332 – 1
APPLICATION
PVC insulated flexible hook -up wires are used for the connection for low voltage applications, communication apparatus, electronic assemblies and equipment, racks, switchboards etc . correspondingly of VDE 0800 part 1 for the temperature range up to +70°C . Those stranded hook -up wires are not permitted to install for heavy current application outside of the equipment
LiYvDIMENSION
|
Cross section area |
Outer diameter approx. |
Copper weight |
|
mm² |
mm |
kg / km |
|
0.14 |
1.1 |
1.4 |
|
0.25 |
1.3 |
2.4 |
|
0.5 |
1.8 |
4.8 |
|
0.75 |
2.0 |
7.2 |
|
1 |
2.1 |
9.6 |
|
1.5 |
2.6 |
14.4 |


